2012年7月11日委员会条例(EU) No 622/2012,修订条例(EC) No 641/2009,该条例关于独立式无轴封循环器和与产品整合的无轴封循环器的生态设计要求(1)
技术法规类型:欧盟Eurlex法规 来源:tbtmap
EURLEX ID:32012R0622
OJ编号:OJ L 180, 12.7.2012, p. 4-8
中文标题:2012年7月11日委员会条例(EU) No 622/2012,修订条例(EC) No 641/2009,该条例关于独立式无轴封循环器和与产品整合的无轴封循环器的生态设计要求(1)
原文标题:Commission Regulation (EU) No 622/2012 of 11 July 2012 amending Regulation (EC) No 641/2009 with regard to ecodesign requirements for glandless standalone circulators and glandless circulators integrated in products (1)
分类:12.10.20_合理利用与节约能源
文件类型:二级立法 Regulation|条例
生效日期:2012-08-01
废止日期:2058-12-31
法规全文:查看欧盟官方文件
EN
Official Journal of the European Union
12.7.2012
COMMISSION REGULATION (EU) No 622/2012
of 11 July 2012
amending Regulation (EC) No 641/2009 with regard to ecodesign requirements for glandless
standalone circulators and glandless circulators integrated in products
(Text with EEA relevance)
THE EUROPEAN COMMISSION,
2. This
Regulation
shall
not
apply
to:
Having regard to the Treaty on the Functioning of the European
(a) drinking water circulators, except as regards the product
Union,
information requirements of Annex I, point 2(1)(d);
Having regard to Directive 2009/125/EC of the European
(b) circulators integrated in products and placed on the
Parliament and of the Council of 21 October 2009 establishing
market no later than 1 January 2020 as replacement
a framework for the setting of ecodesign requirements for
for identical circulators integrated in products and
energy-related products ( 1 ), and in particular Article 15(1)
placed on the market no later than 1 August 2015,
thereof,
except as regards the product information requirements
of Annex I, point 2(1)(e).
After consulting the Ecodesign Consultation Forum,
Article 2
Whereas:
Definitions
(1) Article
7
of
Regulation
(EC)
No
641/2009
of
22
July
For the purposes of this Regulation, the following
2009 implementing Directive 2005/32/EC of the
definitions shall apply:
European Parliament and of the Council with regard to
ecodesign requirements for glandless standalone circu
(1) “circulator” means an impeller pump, with or without
lators and glandless circulators integrated in products ( 2 )
pump housing, which has the rated hydraulic output
requires the Commission to review the methodology for
power of between 1 W and 2 500 W and is designed
calculating the energy efficiency index, set out in Annex
for use in heating systems or in secondary circuits of
II, point 2, to that Regulation, for glandless circulators
cooling distribution systems;
integrated in products before 1 January 2012.
(2) “glandless circulator” means a circulator with the rotor
(2) The
review
carried
out
by
the
Commission
as
well
as
directly coupled to the impeller and the rotor immersed
experience gained with the implementation of Regulation
in the pumped medium;
(EC) No 641/2009 revealed the necessity to amend
certain provisions of Regulation (EC) No 641/2009 in
order to avoid unintended impacts on the circulator
(3) “standalone circulator” means a circulator, designed to
markets and on the performance of the products
operate independently from the product;
covered by that Regulation.
(4) “product” means an appliance that generates and/or
(3) The
measures
provided
for
in
this
Regulation
are
in
transfers heat;
accordance with the opinion of the Committee
established by Article 19(1) of Directive 2009/125/EC,
(5) “circulator integrated in a product” means a circulator
designed to operate as part of a product carrying at least
HAS ADOPTED THIS REGULATION:
one of the following design details:
Article 1
(a) the pump housing is designed to be mounted and
used inside a product;
Amendments to Regulation (EC) No 641/2009
Regulation (EC) No 641/2009 is amended as follows:
(b) the circulator is designed to be speed controlled by
the product;
(1) Articles 1 and 2 are replaced by the following:
(c) the circulator is designed for safety features not
‘Article 1
suitable for standalone operation (ISO IP classes);
Subject matter and scope
(d) the circulator is defined as part of product approval
1. This
Regulation
establishes
ecodesign
requirements
for
or product CE marking;
the placing on the market of glandless standalone
circulators and glandless circulators integrated in products.
(6) “drinking water circulator” means a circulator
specifically designed to be used in the recirculation of
( 1 ) OJ L 285, 31.10.2009, p. 10.
water intended for human consumption as defined in
( 2 ) OJ L 191, 23.7.2009, p. 35.
Article 2 of the Council Directive 98/83/EC (*);
EN
12.7.2012 Official
Journal
of
the
European
Union L
180/5
(7) “pump housing” means the part of an impeller pump
The review shall include the assessment of design options
which is intended to be connected to the pipe work of
that can facilitate reuse and recycling.
the heating systems or secondary circuits of the cooling
distribution system.
The results of the review shall be presented to the Ecodesign
Consultation Forum.’;
___________
(*) OJ L 330, 5.12.1998, p. 32.’;
(3) Annexes I and II to Regulation (EC) No 641/2009 are
amended in accordance with the Annex to this Regulation.
(2) Article 7 is replaced by the following:
Article 2
‘Article 7
Entry into force
Revision
This Regulation shall enter into force on the twentieth day
The Commission shall review this Regulation before
following that of its publication in the Official Journal of the
1 January 2017, in the light of technological progress.
European Union.
This Regulation shall be binding in its entirety and directly applicable in all Member States.
Done at Brussels, 11 July 2012.
For the Commission
The President
José Manuel BARROSO
L 180/6
EN
Official Journal of the European Union
12.7.2012
ANNEX
Amendments to Annexes I and II to Regulation (EC) No 641/2009
Annexes I and II to Regulation (EC) No 641/2009 are amended as follows:
(1) Annex I, point 2, is replaced by the following:
‘2. PRODUCT INFORMATION REQUIREMENTS
1. From 1 January 2013:
(a) the energy efficiency index of standalone circulators calculated in accordance with Annex II, shall be
indicated on the name plate and packaging of the standalone circulator and in the technical documentation
of the standalone circulator as follows: “EEI ≤ 0,[xx]”;
(b) the following information shall be provided on standalone circulators and on circulators integrated in
products: “The benchmark for the most efficient circulators is EEI ≤ 0,20.”;
(c) information concerning disassembly, recycling, or disposal at end-of-life of components and materials, shall
be made available for treatment facilities on standalone circulators and on circulators integrated in
products;
(d) for drinking water circulators, the following information shall be provided on the packaging and in the
documentation: “This circulator is suitable for drinking water only”;
(e) for circulators integrated in products and placed on the market no later than 1 January 2020 as
replacement for identical circulators integrated in products and placed on the market no later than
1 August 2015, the replacement product or its packaging shall clearly indicate the product(s) for which
it is intended.
Manufacturers shall provide information on how to install, use and maintain the circulator in order to
minimise its impact on the environment.
The information listed above shall be visibly displayed on freely accessible websites of the circulator manu
facturer.
2. From 1 August 2015, for circulators integrated in products, the energy efficiency index calculated in
accordance with Annex II, shall be indicated on the name plate of the circulator and in the technical
documentation of the product as follows: “EEI ≤ 0,[xx]”.’;
(2) Annex II, point 2, is replaced by the following:
‘2. METHODOLOGY FOR CALCULATING THE ENERGY EFFICIENCY INDEX
The methodology for calculating the energy efficiency index (EEI) for circulators is as follows:
1. Standalone circulators with pump housing shall be measured as a complete unit;
Standalone circulators without pump housing shall be measured with pump housing identical to the pump
housing in which they are intended to be used;
Circulators integrated in products shall be dismantled from the product and measured with a reference
pump housing;
Circulators without pump housing intended to be integrated in a product shall be measured with a reference
pump housing;
where “reference pump housing” means a pump housing supplied by the manufacturer with inlet and outlet
ports on the same axis and designed to be connected to the pipework of a heating system or secondary
circuit of a cooling distribution system.
2. Where a circulator has more than one setting of head and flow, measure the circulator at the maximum
setting.
“Head” (H) means head (in metres) produced by the circulator at the specified point of operation.
“Flow” (Q) means the volume flow rate of water through the circulator (m 3 /hr).
3. Find the point where Q H is maximum and define the flow and head at this point as: Q 100 % and H 100 % .
EN
12.7.2012 Official
Journal
of
the
European
Union L
180/7
4. Calculate the hydraulic power P hyd at this point.
“Hydraulic power” means an expression of the arithmetic product of the flow (Q), Head (H) and a constant.
“P hyd ” means hydraulic power delivered by the circulator to the fluid being pumped at the specified point of
operation (in watts).
5. Calculate the reference power as:
P ref = 1,7 P hyd + 17 (1 – e – 0,3 P hyd ), 1 W ≤ P hyd ≤ 2 500 W
“Reference power” means a relation between hydraulic power and power consumption of a circulator, taking
into account the dependency between circulator efficiency and size.
“P ref ” means the reference power (in watts) of the circulator in a given head and flow.
6. Define the reference control curve as the straight line between the points:
H
(Q
100 %
100 % , H 100 % ) and ( Q 0 % ,
2 )
7. Select a setting of the circulator ensuring that the circulator on the selected curve reaches Q H = max point.
For circulators integrated in products follow the reference control curve by adjusting the system curve and
speed of the circulator.
“System curve” means a relationship between flow and head (H = f(Q)) resulting from friction in the heating
system or cooling distribution system, as presented in the following graph:
L 180/8
EN
Official Journal of the European Union
12.7.2012
8. Measure P 1 and H at the flows:
Q 100 % , 0,75 Q 100 % , 0,5 Q 100 % , 0,25 Q 100 %
“P 1 ” means the electrical power (in watts) consumed by the circulator at the specified point of operation.
9. Calculate P L as follows:
H
P
ref
L
P
H
1;meas , if H meas ≤ H ref
meas
P L = P 1,meas , if H meas > H ref
Where H ref is the head on the reference control curve at the different flows.
10. Using the measured values of P L and this load profile:
Flow [%] Time
[%]
100
6
75 15
50 35
25 44
Calculate the weighted average power P L,avg as:
P L,avg = 0,06 P L, 100 % + 0,15 P L, 75 % + 0,35 P L, 50 % + 0,44 P L, 25 %
Calculate the energy efficiency index (*) as:
P
EEI
L
;avg C
P
20 % , where C 20 % = 0,49
ref
Except for circulators integrated in products designed for primary circuits of thermal solar systems and for
heat pumps, where the energy efficiency index is calculated as:
P
EEI
L
;avg C
P
20 %
ref
1 – e – 3,8 n s 30 1,36
where C 20 % = 0,49 and n s is the specific speed defined as
n
p
n
100 %
s
60 H 0,75
100 %
Q 100 %
where
n s
[rpm] is specific speed of a circulator;
n 100 % is rotational speed in rpm in this duty defined at Q 100 % and H 100 %.
___________
(*) C XX % means a scaling factor that ensures that at the time of defining the scaling factor only XX % of circulators of
a certain type have an EEI ≤ 0,20.’.
Document Outline
附件:
托管标准,您可以接收以下服务:
1 标准定期系统查新,若有最新版本,会以站内短信或邮件的形式通知用户;
2 随时在标准托管页面中查看到该条标准的最新状态;
3 若用户有在学习和科研中的需要,可以在标准托管页面中试阅标准;
4 企业如果需要上新产品,我院及时提供标准查询、采购等方面的支持;
5 为企业在标准制修订、企业良好行为创建以及标准化试点过程中遇到的困难,可联系我院指定相关专家负责进行指导帮助、提供政策咨询;
6 为企业提供标准化政策的解读、标准化知识的推广培训、标准自我公开声明、标准文献的免费查询、企业标准化体系建设等方面的标准化服务;
标准资讯点击排行榜 全部
资讯标题点击
[[ n.title ]] [[ n.read ]]大连标准化公共服务平台
版权:大连标准化研究院有限公司
地址:大连市中山区高原街56号
电话:0411-82740851